Backflow Testing

Prefabricated pump and piping assembly built in the Wilkes fabrication shop
Our services

Certified Backflow Testing Ohio Water Suppliers Accept

Wilkes Plumbing and Heating performs backflow testing Ohio water suppliers accept, for commercial, industrial, healthcare and school customers in Huron, Sandusky, Norwalk, Port Clinton, Vermilion, Lorain and Fremont. Our testers work on reduced pressure principle assemblies, double check valve assemblies, vacuum breakers and the detector assemblies on fire service lines, then file the report your water department is waiting for.

The test is only the start. When an assembly fails, we rebuild or replace it and retest, and we plan the shutdown around production runs, surgery schedules and school calendars instead of dropping pressure without warning.

Wilkes has worked in the mechanical trades from Huron since 1912. Backflow work sits inside a full plumbing and HVAC shop, so when a failed device turns out to be a symptom of a larger cross connection problem, the same crew corrects the piping.

What a backflow test covers

Our services

Assemblies we test and buildings we serve

Assemblies and devices

  • Reduced pressure principle assemblies
  • Double check valve assemblies
  • Pressure and spill resistant vacuum breakers
  • Fire line detector check assemblies
  • Boiler feed and makeup connections

Buildings we serve

  • Hospitals and outpatient clinics
  • Schools and college campuses
  • Chemical, paint and plastics plants
  • Food and beverage processors
  • Warehouses and office buildings

Backflow testing Ohio requirements: who is covered and how often?

If your building has a service connection that could push water back toward the public main, the water supplier holds you responsible for protecting it. Ohio Administrative Code Chapter 3745-95 places cross connection control on the public water system, which is why the test notice arrives from your city water department rather than from the state. The Ohio EPA backflow prevention program sets what those suppliers have to enforce.

In practice, every backflow prevention assembly on a commercial, industrial or institutional service is tested by a certified tester on the supplier’s cycle, usually once a year, and the report goes back to the supplier. Suppliers in Erie, Huron, Lorain, Ottawa and Sandusky counties each run their own notice schedule, so a company with buildings in Sandusky and Norwalk can sit on two different calendars. We track the due dates so nobody in your office has to.

What happens during a commercial backflow test?

A test is a short, measured procedure, not a look at the device. The tester closes the downstream shutoff, connects a calibrated differential pressure gauge to the test cocks, and reads each check valve and, on a reduced pressure assembly, the relief valve.

  • The first check has to hold a measurable differential against the direction of flow.
  • The second check has to hold tight under back pressure.
  • On a reduced pressure principle assembly, the relief valve has to open before the differential across the first check falls below 2 psid.

Assemblies are built and listed to standards published by ASSE International, including ASSE 1013 for reduced pressure principle assemblies and ASSE 1015 for double check valve assemblies. A gauge that has drifted out of calibration will write a passing report on a failing device, so gauge calibration is kept on its own schedule.

Which assembly belongs on which connection?

Degree of hazard drives the choice. A connection that could return a health hazard, such as a chemical feed line, a boiler carrying treatment chemicals, an irrigation main or a laboratory bench, needs a reduced pressure principle assembly. A connection with no health hazard, such as a closed loop with no additives, may be protected by a double check valve assembly. Cross connection control practice published by the American Water Works Association is the reference most Ohio suppliers work from.

Hospitals raise the count quickly, because sterilizers, dialysis, lab benches, cooling towers and food service each carry their own protection. Wilkes has performed mechanical work at Firelands Regional Medical Center in Sandusky, and our healthcare mechanical group plans this work around occupied departments.

Why do assemblies fail during Lake Erie winters?

Freeze damage is the leading failure we find. A reduced pressure principle assembly is designed to discharge through its relief valve, so it cannot sit anywhere that discharge will freeze or flood. Assemblies in unheated vestibules, loading docks and outdoor enclosures split when a January cold snap comes off Lake Erie and the enclosure heater has been dead since fall.

Debris is the second. Scale and grit off older mains land on a rubber check disc and hold it open by a few thousandths of an inch, which is enough to fail the test even though the device looks fine. Our commercial plumbing maintenance checklist covers the seasonal walkthrough that catches both, and our article on backflow testing rules in Ohio goes further into the paperwork.

How does a backflow prevention assembly repair get scheduled?

A failed assembly is usually rebuilt rather than replaced. We carry rebuild kits for the common makes and sizes, so a fouled check or a worn relief valve seat is often corrected on the same visit and retested before the crew leaves. Replacement earns its cost when the body is cracked, the assembly is undersized for current demand, or parts for the model are no longer made.

Either way the water is off for a while, and that is the part worth planning. Where the supplier will allow a temporary bypass, we arrange it in advance. This work runs through the same crews as our commercial plumbing and commercial plumbing and HVAC service, from Sandusky east to Lorain and west to Fremont.

Schedule your annual backflow test

Send us the notice from your water department and we will handle the rest. Call (419) 433-2325, email info@wilkesandcompany.com, or request a quote with the building address and the number of assemblies. Our office in Huron is open Monday through Friday, 8:00 AM to 4:00 PM.

Frequently asked questions

How often does a backflow preventer have to be tested in Ohio?

Public water suppliers set the cycle under their cross connection control rules, and in almost every Ohio community that means an annual test by a certified tester, with the report filed back to the water department. Some suppliers test high hazard connections more often. Check the notice you receive, since the deadline on it governs.

What makes a backflow assembly fail a test?

The common causes are debris holding a check disc open, worn or hardened rubber, a relief valve that opens late or leaks continuously, fouled test cocks, and freeze damage to the body. Most of these are rebuild items rather than replacement items, and a rebuilt assembly is retested on the spot before the report is written.

Do you handle backflow preventer testing in Sandusky, Ohio?

Yes. Sandusky is a few minutes from our Huron office, and we test and repair assemblies for plants, hospitals, schools and commercial buildings throughout Erie County. We also cover Norwalk, Port Clinton, Vermilion, Lorain and Fremont, and the surrounding Huron, Lorain, Ottawa and Sandusky county communities.

How long does the water have to be shut off?

A routine test on a single assembly takes roughly 20 to 30 minutes of shutdown for that service. A rebuild adds time, and larger fire line assemblies take longer because of the coordination involved. We agree on the window before we arrive, and for hospitals and food plants we will work off hours to protect the schedule.

Can you correct the cross connection, not just test the device?

Yes. A failing device sometimes points at piping that was never protected correctly, such as a chemical feed added years after the original build. Because Wilkes runs a full plumbing, process piping and HVAC shop, the same crew can repipe the connection, set the right assembly for the hazard, and test it once the work is done.